ITAWATT Force A100
ITAWATT Force A100
Features
100 kWh Energy Storage Capacity
Provides substantial energy-storage capacity for commercial facilities, industrial operations, solar installations and backup-power applications.
Safe LiFePO4 Battery Technology
Lithium Iron Phosphate chemistry offers strong thermal stability, dependable performance and enhanced operational safety.
Intelligent Air Cooling
An integrated air-cooling system helps regulate operating temperature and maintain stable performance during charging and discharging.
100 kWh Energy Storage Capacity
Provides substantial energy-storage capacity for commercial facilities, industrial operations, solar installations and backup-power applications.
Safe LiFePO4 Battery Technology
Lithium Iron Phosphate chemistry offers strong thermal stability, dependable performance and enhanced operational safety.
Intelligent Air Cooling
An integrated air-cooling system helps regulate operating temperature and maintain stable performance during charging and discharging.
Smart Energy Management
Supports peak shaving, valley filling, electricity-price arbitrage, photovoltaic priority and other intelligent operating strategies.
Anti-Backflow and Black-Start Support
Anti-Backflow and Black-Start Support
Commercial-Grade Construction
A robust cabinet design protects internal components and supports installation in demanding commercial and industrial environments.
ITAWATT Technical Specifications
| Specification | Technical Data |
|---|---|
| Product Name | ITAWATT FORCE A100 |
| System Type | Commercial & Industrial Air-Cooled BESS |
| Rated Energy | 100 kWh |
| Battery Chemistry | Lithium Iron Phosphate (LiFePO4) |
| Battery Configuration | 100S1P |
| Rated Capacity | 314 Ah |
| Nominal Battery Voltage | 320 V |
| Battery Voltage Range | 280–360 V |
| Maximum DC Power | 50 kW |
| Maximum Battery Current | 157 A |
| Maximum AC Apparent Power | 35.2 kVA |
| AC Active Power | 32 kW |
| Rated AC Voltage | 400 V |
| Rated AC Current | 46 A |
| AC Voltage Range | 320–460 V |
| Rated Frequency | 50/60 Hz |
| Frequency Range | 45–55 Hz / 55–65 Hz |
| Total Harmonic Distortion (THDi) | <3% |
| Power Factor | 1.0, adjustable from 0.8 leading to 0.8 lagging |
| AC System | Three-phase, four-wire |
| Overload Capability | 110% |
| Cooling Method | Intelligent Air Cooling |
| Optional STS Power | 50 kW |
| STS Voltage and Frequency | 400 V, 50/60 Hz |
| STS Overload Capability | 110% |
| STS Transfer Time | <20 ms |
| System Functions | Anti-backflow and black start |
| Operating Strategies | Peak shaving, valley filling, electricity-price arbitrage, photovoltaic priority and off-grid power supply |
Advantages

Lower Electricity Costs
Reliable Backup Power

Reliable Backup Power